2.2.3 Installing the Servopack

22

2.2.3 Installing the Servopack

Σ-Series DR2 Servopack is a rack−mounted type ser-
vo controller.
Incorrect installation will cause problems. Always ob-
serve the installation instructions described in the next
page.

Storage:

When the Servopack is to be stored with the power cable disconnected, store it in the
following temperature range:

Between −20°C and 85°C

Installation sites:

Situation

Notes on Installation

When installed in a control panel

Design the control panel size, unit layout, and cooling
method so that the temperature around the periphery of
the Servopack does not exceed 55°C.

When installed near a heating
unit

Suppress radiation heat from the heating unit and a
temperature rise caused by convection so that the
temperature around the periphery of the Servopack does
not exceed 55°C.

When installed near a source of
vibration

Install a vibration isolator underneath the Servopack to
prevent it from receiving vibration.

When installed in a place
receiving corrosive gases

Corrosive gases do not immediately affect the Servopack
but will eventually cause contactor-related devices to
malfunction. Take appropriate action to prevent corrosive
gases.

Others

Avoid installation in a hot and humid place or where
excessive dust or iron powder is present in the air.

Orientation:

Install the Servopack perpendicularly as shown in
the figure.

The Servopack must be orientated as shown in
the figure because it is designed to be cooled by
natural convection.

• Firmly secure the Servopack through three or

four mounting holes.

2

DR2 Servopack

Ventilation