Figure 3-2, Grounding lugs at the system's rear – Artesyn Centellis 4100 Installation and Use (2015) User Manual

Page 86

background image

System Installation

Centellis 4100 Installation and Use (6806800D82E)

88

Procedure

To ground the system proceed as follows:

1. Connect the rack ground lug to the M6 shelf ground at the bottom right rear of the

shelf and torque the shelf ground lug nut to maximum. The studs are spaced 19
mm (0.75 inch) apart. This distance allows the use of anti-rotating two-hole lugs.
They are marked with the corresponding grounding symbol. Artesyn Embedded

Technologies - Embedded Computing recommends to use the cable from

Thomas&Betts as described in the chapter

Tools You Will Need

on page 82

or an

equivalent cable.

2. Permanantly connect to the earth ground of the building.

Figure 3-2

Grounding Lugs at the System's Rear