Site Preparation

Centellis 4100 Installation and Use (6806800D82E)

68

Shock

Half-sine, 11 ms, 30 m/s

2

Blade level packaging
Half-sine, 6 ms at 180 m/s

2

Vibration
(tested in
target
platform)

0.1g from 5 Hz to 100 Hz and back to 5 Hz at a
rate of 0.1 octave/minute

5-20 Hz at 0.01 g

2

/Hz

20-200 Hz at -3.0 dB/octave
Random 5-20 Hz at 1m

2

/s

3

Random 20-200 Hz at -3 dB/octave

Free fall

-

300mm (11.8 in) (packaged)
25mm (1 in) (unpackaged) per GR-63-
CORE
fully populated system

Noise

ETSI ETS 300 753 (October 1997)
Telecommunication equipment rooms
(attended): 7.2 bel
Measurement of "declared A-weight sound
power level"
All values are applicable to normal operating
conditions (~23°C).

NEBS GR-63-CORE, Issue 3
Telecommunication equipment rooms
(attended): 78 dB
Measurement of "declared A-weight sound
power level"
All values are applicable to normal operating
conditions (~27°C).

-

The ambient temperature around the shelf and the air inlet temperature must not
exceed 55°C (131°F).

The Centellis 4100 system regulates the blower speed based on the temperature
sensors present in the system. The blower speed is adjusted to the lowest speed which
still keeps the evaluated temperature readings below or at their respective "upper non-
critical threshold". Hence, the blower speed depends on the ambient temperature, blade
design, temperature threshold settings, and system configuration.

Table 2-1 Environmental Conditions (continued)

Feature

Operating

Non-Operating (packed state)