The A1 and B1 PEM locations are capable of supplying 90A of current although the PEMs will
only allow for 50A. The A2 and B2 PEM locations are capable of supplying 50A. This allows for
a single PEM in each interconnect to support the full power requirement of the interconnect.

For the blowers, the A1 and B1 feeds are capable of supplying 12A when derated for a 30ºC
temperature rise. For the ShMCs, the A1 and B1 feeds are limited by the 2 mm connector to
approximately 1.5A (per feed).