Table 2-2, Critical temperature limits, Site preparation – Artesyn Centellis 4100 Installation and Use (2015) User Manual
Page 67

Site Preparation
Centellis 4100 Installation and Use (6806800D82E)
69
To guarantee proper blade operation, you have to make sure that the temperatures at the
locations specified in the following are not exceeded. If not stated otherwise, the temperatures
should be measured by placing a sensor exactly at the given locations. For your convenience all
temperature spots are shown in the figures below.
Table 2-2 Critical Temperature Limits
Component
Temperature Limit
Air inlet (system’s front)
55°C (131 °F)
Air outlet (system’s rear)
70°C (158 °F)
Power entry module lug-plastic washer
70°C (158 °F)
>70°C (158 °F) and maximum 90°C (194 °F): the
cables must be isolated and must be approved to be
used in this temperature range.
>70°C (158 °F) and maximum 90° (194 °F): the
service personel may touch the components: the
cables must be isolated and the "hot surface" icon
must be attached. The cables must be approved to
be used in this temperature range.
- AXP640 Installation and Use (April 2015) AXP1620 Installation and Use (August 2014) AXP1620 Installation and Use (September 2014) Centellis-4440/AXP-1440 Installation and Use (August 2014) Centellis-4440/AXP-1440 Installation and Use (July 2014) AXP1620 Installation and Use (May 2014) Centellis-4440/AXP1440 Installation and Use (August 2014) Centellis-4440/AXP-1440 Installation and Use (May 2014) Centellis-4440/AXP1440 Installation and Use (September 2014) AXP640 Installation and Use (May 2014)