Site Preparation

Centellis 4100 Installation and Use (6806800D82E)

69

To guarantee proper blade operation, you have to make sure that the temperatures at the
locations specified in the following are not exceeded. If not stated otherwise, the temperatures
should be measured by placing a sensor exactly at the given locations. For your convenience all
temperature spots are shown in the figures below.

Table 2-2 Critical Temperature Limits

Component

Temperature Limit

Air inlet (system’s front)

55°C (131 °F)

Air outlet (system’s rear)

70°C (158 °F)

Power entry module lug-plastic washer

70°C (158 °F)
>70°C (158 °F) and maximum 90°C (194 °F): the
cables must be isolated and must be approved to be
used in this temperature range.
>70°C (158 °F) and maximum 90° (194 °F): the
service personel may touch the components: the
cables must be isolated and the "hot surface" icon
must be attached. The cables must be approved to
be used in this temperature range.