1 installing the system in a rack, Installing the system in a, Rack – Artesyn Centellis 4100 Installation and Use (2015) User Manual
Page 82

System Installation
Centellis 4100 Installation and Use (6806800D82E)
84
3.3.1
Installing the System in a Rack
The following procedure describes how to install the system in a rack.
System Damage
Environmental contamination can impair system operation.
Locate the system in a stable area free of movement and free of dust, smoke, and
electrostatic discharge (ESD). Make sure, that the temperature does not exceed the
operating temperature given in the environmental requirements in this manual and allow
room for proper air cooling.
System Overheating
Improper cooling leads to blade damage.
To ensure proper cooling always operate the system in a horizontal position. Furthermore,
keep clear at least 6 cm adjacent to the cooling vents on the chassis front and back side.
Use power input cables with a cross section (minimum) of 10 mm
2
, AWG 6.
- AXP640 Installation and Use (April 2015) AXP1620 Installation and Use (August 2014) AXP1620 Installation and Use (September 2014) Centellis-4440/AXP-1440 Installation and Use (August 2014) Centellis-4440/AXP-1440 Installation and Use (July 2014) AXP1620 Installation and Use (May 2014) Centellis-4440/AXP1440 Installation and Use (August 2014) Centellis-4440/AXP-1440 Installation and Use (May 2014) Centellis-4440/AXP1440 Installation and Use (September 2014) AXP640 Installation and Use (May 2014)