System Installation
Centellis 4100 Installation and Use (6806800D82E)
83
Observe the following general safety notes when installing your system:
Restricted access area - The system is only to be installed in a restricted access area.
Installation codes - This unit must be installed in accordance with the National
Electrical Code, Articles 110.16, 110.17, and 110.18 and the Canadian Electrical Code,
Section 12.
Conductor ampacity - According to UL 60950, Annex NAE (NEC Article 645-5(a)), the
branch-circuit conductors supply must have an ampacity of not less than 125% of the
total connected load. Per NEC Article 310.15 and Table 310.16, the minimum
American Wire Gauge (AWG) has to be selected.
Overcurrent protection - A readily accessible listed branch-circuit overcurrent
protective device must be incorporated into the building wiring.
Artesyn Embedded Technologies - Embedded Computing is not responsible for
regulatory compliance or malfunction of any user-modified product.
- AXP640 Installation and Use (April 2015) AXP1620 Installation and Use (August 2014) AXP1620 Installation and Use (September 2014) Centellis-4440/AXP-1440 Installation and Use (August 2014) Centellis-4440/AXP-1440 Installation and Use (July 2014) AXP1620 Installation and Use (May 2014) Centellis-4440/AXP1440 Installation and Use (August 2014) Centellis-4440/AXP-1440 Installation and Use (May 2014) Centellis-4440/AXP1440 Installation and Use (September 2014) AXP640 Installation and Use (May 2014)