2.2.4
Dimensions and Weight
The table below lists the dimenstions and weight of the shelf and system components.
Table 2-3 System Power Requirements
Feature Value
Rated voltage and input current
81-67A at -48 to -60VDC
US and Canada: 81A at -48VDC
Operating voltage range
-40.0 to -72VDC
US and Canada: -40.0VDC to -60VDC
Maximum power dissipation
The power distribution is tested for supplying 215W/front
slot to all slots simultaneously and additionally 25W/rear
slot.
When installing additional blades or modules, make sure that the power consumption of all
installed modules does not exceed the system's maximum power dissipation.
The maximum weight of the system must not exceed 80 kg.
Table 2-4 Dimensions and Weight of System and Components
Component
Dimensions
w x h x d in mm
Weight in kg
Shelf, including four blowers, four PEMs, air filter
483 x 575 x 505
34,00
PEM
69 x 102 x 138
0,96
Blower
210 x 42 x 215
1,72
- AXP640 Installation and Use (April 2015) AXP1620 Installation and Use (August 2014) AXP1620 Installation and Use (September 2014) Centellis-4440/AXP-1440 Installation and Use (August 2014) Centellis-4440/AXP-1440 Installation and Use (July 2014) AXP1620 Installation and Use (May 2014) Centellis-4440/AXP1440 Installation and Use (August 2014) Centellis-4440/AXP-1440 Installation and Use (May 2014) Centellis-4440/AXP1440 Installation and Use (September 2014) AXP640 Installation and Use (May 2014)