beautypg.com

4 dimensions and weight, Table 2-3, System power requirements – Artesyn Centellis 4100 Installation and Use (2015) User Manual

Page 71: Table 2-4, Dimensions and weight of system and components, Site preparation

background image

Site Preparation

Centellis 4100 Installation and Use (6806800D82E)

73

2.2.4

Dimensions and Weight

The table below lists the dimenstions and weight of the shelf and system components.

Table 2-3 System Power Requirements

Feature Value

Rated voltage and input current

81-67A at -48 to -60VDC
US and Canada: 81A at -48VDC

Operating voltage range

-40.0 to -72VDC
US and Canada: -40.0VDC to -60VDC

Maximum power dissipation

The power distribution is tested for supplying 215W/front
slot to all slots simultaneously and additionally 25W/rear
slot.

When installing additional blades or modules, make sure that the power consumption of all
installed modules does not exceed the system's maximum power dissipation.

The maximum weight of the system must not exceed 80 kg.

Table 2-4 Dimensions and Weight of System and Components

Component

Dimensions
w x h x d in mm

Weight in kg

Shelf, including four blowers, four PEMs, air filter

483 x 575 x 505

34,00

PEM

69 x 102 x 138

0,96

Blower

210 x 42 x 215

1,72