Drive ratings – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9-14 Drives Installation - A4 Size User Manual
Page 179

Specifications
A-5
Drive Ratings
The tables on the following pages provide drive ratings (including
continuous, 1 minute and 3 seconds), PWM frequency ratings, ambient
operating temperatures and watts loss information.
Table A.A 400 Volt AC Input Frames 9 - 14 Drive Ratings
Drive Catalog
Number
Fr
ame kW Rating
PWM
Freq.
Temp.
Input
Ratings
Output Amps
Watts
Loss
ND
HD
kHz
°
C
Amps
Cont.
1 Min.
3 Sec.
Watts
20xC261
9
132
-
2
40
263
261
287
410
2700
-
110
2
40
207
205
308
410
2700
20xC300
9
160
-
2
40
302
300
330
450
3100
-
132
2
40
247
245
368
490
3100
20xC385
10
200
-
2
40
388
385
424
600
4320
-
160
2
40
302
300
450
600
4320
20xC460
10
250
-
2
40
463
460
506
770
5335
-
200
2
40
388
385
578
770
5335
20xC500
10
250
-
2
40
504
500
550
750
5921
-
250
2
40
423
420
630
840
5921
20xC590
11
315
-
2
40
594
590
649
956
6620
-
250
2
40
524
520
780
956
6620
20xC650
11
355
-
2
40
655
650
715
1062
7538
-
315
2
40
594
590
885
1062
7538
20xC730
11
400
-
2
40
735
730
803
1095
8312
-
355
2
40
655
650
975
1170
8312
20xC820
12
450
-
2
40
826
820
902
1230
9201
-
400
2
40
735
730
1095
1314
9201
20xC920
12
500
-
2
40
927
920
1012
1380
10670
-
450
2
40
826
820
1230
1476
10670
20xC1K0
12
560
-
2
40
1038
1030
1133
1555
11729
-
500
2
35
927
920
1370
1600
11729
20xC1K1
13
630
-
2
40
1158
1150
1265
1620
13801
-
560
2
40
1038
1030
1545
1620
13801
20xC1K3
13
710
-
2
40
1310
1300
1430
2079
15077
-
630
2
40
1158
1150
1725
2079
15077
20xC1K4
13
800
-
2
40
1461
1450
1595
2175
16511
-
710
2
40
1209
1200
1800
2400
16511
20xC1K7
(1)
(1)
Not available with 700S Control.
14
1000
-
2
40
1783
1770
1947
2655
24800
-
900
2
40
1612
1600
2400
2880
24800
20xC2K1
(1)
14
1200
-
2
40
2166
2150
2365
3225
29900
-
1100
2
40
1954
1940
2910
3492
29900
20xC2K7
(1)
14
1600
-
2
40
2720
2700
2970
3933
39680
-
1300
2
40
2317
2300
3287
3933
39680