Frame 11 Installation

Figure 8.2 Enclosure Code B (NEMA/UL Type 1, IP21) and K (NEMA/UL Type 1, IP21
w/Conformal Coat)

Operating Temperatures

Frame 11 drives require a minimum of 3900 m

3

/h (2295 cfm) of cooling air.

200 mm

(7.

8

7 in.) Min.

838

mm

(

33

.0 in.) Min.

PowerFlex Drive

Voltage Class

Amp Rating

Surrounding Air Temperature
Normal Duty

Heavy Duty

700H

All

All

0 to 40

°

C

(32 to 104

°

F)

0 to 40

°

C

(32 to 104

°

F)

700S

400/480V AC
(540/650V DC)

All

0 to 40

°

C

(32 to 104

°

F)

0 to 40

°

C

(32 to 104

°

F)

600/690V AC
(810/932V DC)

460, 502

0 to 40

°

C

(32 to 104

°

F)

0 to 40

°

C

(32 to 104

°

F)

600/690V AC
(810/932V DC)

590

0 to 35

°

C

(32 to 95

°

F)

0 to 35

°

C

(32 to 95

°

F)

This manual is related to the following products: