1-6

General Installation Information

Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC
Drives
, publication DRIVES-IN001…).

Interlocked armor is acceptable for shorter cable runs, but continuous
welded armor is preferred.

Best performance is achieved with three spaced ground conductors, but
acceptable performance below 200 HP is provided via a single ground
conductor.

Table 1.B Recommended Shielded / Armored Cable

EMC Compliance

Refer to

EMC Instructions

for details.

CabIe Trays and Conduit

If cable trays or large conduits are to be used, refer to guidelines presented
in publication DRIVES-IN001… , Wiring and Grounding Guidelines for
Pulse Width Modulated (PWM) AC Drives
.

Location

Rating/Type

Description

Standard
(Option 1)

600V, 90

°

C (194

°

F)

XHHW2/RHW-2
Anixter B209500-B209507,
Belden 29501-29507, or
equivalent

Four tinned copper conductors with XLPE insulation.

Copper braid/aluminum foil combination shield and
tinned copper drain wire.

PVC jacket.

Standard
(Option 2)

Tray rated 600V, 90

°

C (194

°

F) RHH/RHW-2
Anixter OLF-7xxxxx or
equivalent

Three tinned copper conductors with XLPE insulation.

5 mil single helical copper tape (25% overlap min.) with
three bare copper grounds in contact with shield.

PVC jacket.

Class I & II;
Division I & II

Tray rated 600V, 90

°

C (194

°

F) RHH/RHW-2
Anixter 7V-7xxxx-3G or
equivalent

Three bare copper conductors with XLPE insulation
and impervious corrugated continuously welded
aluminum armor.

Black sunlight resistant PVC jacket overall.

Three copper grounds on #10 AWG and smaller.

!

ATTENTION: To avoid a possible shock hazard caused by
induced voltages, unused wires in the conduit must be grounded
at both ends. For the same reason, if a drive sharing a conduit is
being serviced or installed, all drives using this conduit should be
disabled. This will help minimize the possible shock hazard from
“cross coupled” motor leads.