2-8

PowerFlex

®

700H Control Wiring

Analog Input Bipolar
Speed Reference

±

10V Input

Set I/O configuration (refer to

Analog I/O Configuration on
page 2-6

).

Set parameter 190 [Direction Mode]
= 1 “Bipolar”

Adjust Scaling:
Parameters 91 [Speed Ref A Hi] /
92 [Speed Ref A Lo] and 325
[Analog In 2 Hi] / 326 [Analog In 2
Lo]

View Results:
Parameter 002 [Commanded
Speed]

Analog Voltage Input
Unipolar Speed
Reference

0

to

+

10V Input

Set I/O configuration (refer to

Analog I/O Configuration on
page 2-6

).

Configure Input with parameter 320
[Anlg In Config]

Adjust Scaling:
Parameters 91 [Speed Ref A Hi] /
92 [Speed Ref A Lo] and 325
[Analog In 2 Hi] / 326 [Analog In 2
Lo]

View Results:
Parameter 002 [Commanded
Speed]

Analog Current Input
Unipolar Speed
Reference
4-20 mA Input

Set I/O configuration (refer to

Analog I/O Configuration on
page 2-6

).

Configure Input for Current:
Parameter 320 [Anlg In Config] and
add jumper at appropriate terminals

Adjust Scaling:
Parameters 91 [Speed Ref A Hi] /
92 [Speed Ref A Lo] and 325
[Analog In 2 Hi] / 326 [Analog In 2
Lo]

View Results:
Parameter 002 [Commanded
Speed]

Analog Input, PTC
0-10V Input
PTC OT set > 5V
PTC OT cleared < 5V
PTC Short < 0.2V

Set I/O configuration (refer to

Analog I/O Configuration on
page 2-6

).

Configure Analog Input for PTC
function:
Set parameter 259 [Alarm Config 1]
bit 14 “PTC Config” = Enabled

Configure Analog Input for Fault
when input goes below 0.2V:
Set parameter 324 [Analog In 1
Loss] = 1 “Fault”

Enable Fault:
Set parameter 238 [Fault Config 1]
bit 7 “Motor Therm” = Enabled

Enable Alarm:
Set parameter 259 [Alarm Config
1], bit 11 “Motor Therm” = Enabled

Input/Output

Connection Example

Required Parameter Changes

3
4

3
4

3
4

6

3.32k

Ohm

1.8k

PTC

Ferrite

Bead

1

7

2