beautypg.com

Rockwell Automation 20D PowerFlex 700H and 700S Frame 9-14 Drives Installation - A4 Size User Manual

Page 40

background image

3-2

Control Wiring for PowerFlex 700S Drives with Phase I Control

Standard
Analog I/O

Belden 8760/9460(or equiv.)

0.750 mm

2

(18AWG),

twisted pair, 100% shield
with drain

(5)

.

300V,
75-90

º

C

(167-194

º

F)

Remote Pot Belden 8770(or equiv.)

0.750 mm

2

(18AWG), 3

cond., shielded

Encoder/
Pulse I/O
Less 30.5 m
(100 ft.)

Combined:

Belden 9730 (or equivalent)

(1)

0.196 mm

2

(24AWG),

individually shielded.

Encoder/
Pulse I/O
30.5 m (100
ft.) to 152.4
m (500 ft.)

Signal:

Belden 9730/9728 (or
equivalent)

(1)

0.196 mm

2

(24AWG),

individually shielded.

Power:

Belden 8790

(2)

0.750 mm

2

(18AWG)

Combined:

Belden 9892

(3)

0.330 mm

2

or 0.500 mm

2

(3)

Encoder/
Pulse I/O
152.4 m
(500 ft.) to
259.1 m
(850 ft.)

Signal:

Belden 9730/9728 (or
equivalent)

(1)

0.196 mm

2

(24AWG),

individually shielded.

Power: Belden

8790

(2)

0.750 mm

2

(18AWG)

Combined:

Belden 9773/9774 (or
equivalent)

(4)

0.750 mm

2

(18AWG),

individually shielded pair.

EMC
Compliance

Refer to

EMC Instructions on page 1-7

for details.

(1)

Belden 9730 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9728
(or equivalent).

(2)

Belden 8790 is 1 shielded pair.

(3)

Belden 9892 is 3 individually shielded pairs (3 channel), 0.33 mm

2

(22 AWG) plus 1 shielded pair 0.5 mm

2

(20

AWG) for power.

(4)

Belden 9773 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9774
(or equivalent).

(5)

If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire
may not be necessary, but is always recommended.

Type

Wire Type(s)

Description

Insulation
Rating

This manual is related to the following products: