background image

Frame 14 Installation

11-25

Circuit Breaker DIP Switch Settings

The DIP switches on the circuit breakers are configured to the correct
settings at the factory. However, the settings detailed in

Table 11.C

below

should be verified before charging the circuit breaker motor operators and
operating the drive.

Table 11.C Circuit Breaker DIP Switch Settings

Figure 11.12 Circuit Breaker DIP Switches Location

Voltage Class

Drive ND Cont.
Amp Rating

L

S/I

N

I1

t1

S/I

I3

t2

ON/OFF 50% / 100%

400/480V AC

1770

0.76

3 s

S

1.5

0.1 s

OFF

na

2150

0.92

3 s

S

1.5

0.1 s

OFF

na

600/690V AC

1500

0.88

3 s

S

1.0

0.1 s

OFF

na

1900

0.84

3 s

S

1.0

0.1 s

OFF

na

2250

0.96

3 s

S

1.5

0.1 s

OFF

na

OFF

DI

S

CHARGED

S

PRING

L

S

I

N

L

N

I1 =
In x (0.4+

t1

S

I

t2

I2=
In x
I

3

=

This manual is related to the following products: