Rockwell Automation 20D PowerFlex 700H and 700S Frame 9-14 Drives Installation - A4 Size User Manual
Page 192
![background image](/manuals/580911/192/background.png)
A-18
Specifications
20xF650
12
630
–
655
850
(1 per phs)
425
(2 per phs)
1400
850
(1 per phs)
425
(2 per phs)
1900
170M5813
1900
900
–
560
594
750
(1 per phs)
375
(2 per phs)
1300
750
(1 per phs)
375
(2 per phs)
1700
170M5813
1700
800
20xF750
12
710
–
756
950
(1 per phs)
475
(2 per phs)
1600
950
(1 per phs)
475
(2 per phs)
2200
170M5813
2200
1000
–
630
655
850
(1 per phs)
425
(2 per phs)
1400
850
(1 per phs)
425
(2 per phs)
1900
170M5813
1900
900
20xF820
(1)
12
800
–
826
1100
(1 per phs)
550
(2 per phs)
1800
1100
(1 per phs)
550
(2 per phs)
2400
170M5813
2400
1100
–
630
655
850
(1 per phs)
425
(2 per phs)
1400
850
(1 per phs)
425
(2 per phs)
1900
170M5813
1900
900
20xF920
13
900
–
927
1200
(1 per phs)
600
(2 per phs)
2000
1200
(1 per phs)
600
(2 per phs)
2700
170M6466
(5)
2700
1200
–
800
826
1100
(1 per phs)
550
(2 per phs)
1800
1100
(1 per phs)
550
(2 per phs)
2400
170M6466
(5)
2400
1100
20xF1K0
13
1000
–
1038
1300
(1 per phs)
650
(2 per phs)
2300
1300
(1 per phs)
650
(2 per phs)
3000
170M6466
(5)
3000
1300
–
900
927
1200
(1 per phs)
600
(2 per phs)
2000
1200
(1 per phs)
600
(2 per phs)
2700
170M6466
(5)
2700
1200
20xF1K1
13
1100
–
1189
1500
(1 per phs)
750
(2 per phs)
2600
1500
(1 per phs)
750
(2 per phs)
3500
170M6466
(5)
3500
1500
–
1000
1038
1300
(1 per phs)
650
(2 per phs)
2300
1300
(1 per phs)
650
(2 per phs)
3000
170M6466
(5)
3000
1300
20xF1K5
14
1500
–
1511
1900
(1 per phs)
650
(3 per phs)
3300
1900
(1 per phs)
650
(3 per phs)
4500
170M6466
4500
1900
–
1300
1310
1700
(1 per phs)
575
(3 per phs)
2900
1700
(1 per phs)
575
(3 per phs)
3900
170M6466
3900
1700
20xF1K9
(2)
14
1800
–
1914
2400
(1 per phs)
800
(3 per phs)
4200
2400
(1 per phs)
800
(3 per phs)
5700
170M6466
5700
2400
–
1500
1511
1900
(1 per phs)
650
(3 per phs)
3200
1900
(1 per phs)
650
(3 per phs)
4500
170M6466
4500
1900
20xF2K2
(2)
14
2000
–
2267
2900
(1 per phs)
950
(3 per phs)
5000
2900
(1 per phs)
950
(3 per phs)
6700
170M6466
6700
2900
–
1800
1914
2400
(1 per phs)
800
(3 per phs)
4200
2400
(1 per phs)
800
(3 per phs)
5700
170M6466
5700
2400
(1)
20DF820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
(2)
Not available with 700S Control.
(3)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4)
Maximum protection device size is the highest rated device that supplies drive protection.
(5)
These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.
(6)
Inverse time breaker. Ratings shown are maximum.
(7)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(8)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip
settings must be set to US NEC code. Not to exceed 1300% FLA.
Drive
Catalog
Number
Fr
am
e
kW Rating
Input
Ratings
Dual Element Time Delay Fuse
Non-Time Delay Fuse
Bussmann Style
Semi-Conductor Fuse
Circuit
Breaker
(6)
Motor Circuit
Protector
(8)
ND
HD
Amps
Min.
(3)
Max.
(4)
Min.
(3)
Max.
(4)
Max.
(7)
Max.