Frame 11 Installation

8-13

Power Wiring

AC Input Wiring

The table below identifies which frame 11 drives contain only one
rectifying module and which frame 11 drives contain two rectifying
modules. Drives with one rectifying module contain only one set of input
power terminals. Drives with two parallel rectifying modules contain two
sets of input power terminals--you must supply power to both sets of input
terminals on these drives. There are several methods for accomplishing this.
Each of these methods is shown below.

Important: Parallel wiring must have the same cable dimensions, type and

routing. Non-symmetrical wiring may cause unequal loading
between the converters and reduce the drive’s ability to deliver
current to the motor.

Figure 8.1 AC Wiring Example: Two Fuses per Phase

Voltage Class

Amps

Number of
Rectifiers

400/480V AC Input 590

2

650

2

730

2

600/690V AC Input 460

1

502

1

590

2

1L1

1L2

1L3

2L1

2L2

2L3

L1

L2

L3

AC Input Power Terminals

Inside Drive

AC Input Power Wiring, Fuses, and

Disconnect Device Provided by

Customer