Communication Options
5-5
Figure 5.5 PowerFlex 700S Logic Status Word
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status
Description
x Active
0 = Not Active
1 = Active
x
Running
0 = Not Running
1 = Running
x
Command
Direction
0 = Reverse
1 = Forward
x
Actual
Direction
0 = Reverse
1 = Forward
x
Accel
0 = Not Accelerating
1 = Accelerating
x
Decel
0 = Not Decelerating
1 = Decelerating
x
Jogging
0 = Not Jogging
1 = Jogging
x
Fault
0 = No Fault
1 = Fault
x
Alarm
0 = No Alarm
1 = Alarm
x
Flash Mode 0 = Not in Flash Mode
1 = In Flash Mode
x
Run Ready 0 = Not Ready to Run
1 = Ready to Run
x
At Limit
(1)
(1)
See Parameter 304 - [Limit Status] in the PowerFlex 700S drive for a description of the limit status conditions.
0 = Not At Limit
1 = At Limit
x
Tach Loss
Sw
0 = Not Tach Loss Sw
1 = Tach Loss Sw
x
At Zero Spd 0 = Not At Zero Speed
1 = At Zero Speed
x
At Setpt
Spd
0 = Not At Setpoint Speed
1= At Setpoint Speed
x
Enable
0 = Not Enabled
1 = Enabled