Rockwell Automation 20D PowerFlex 700H and 700S Frame 9-14 Drives Installation - A4 Size User Manual
Page 29
PowerFlex
®
700H Control Wiring
2-3
Figure 2.2 PowerFlex 700H I/O Terminal Blocks & Jumpers
I/O Terminal Blocks
Table 2.D I/O Terminal Block Specifications
No. Name
Description
Wire Size Range
(2)
(2)
Maximum/minimum that the terminal block will accept - these are not recommendations.
Torque
Maximum
Minimum
Maximum
Recommended
➊
Analog I/O
Analog I/O Signals
2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.2 N-m
1.8 lb.-in.
0.2 N-m
1.8 lb.-in.
➋
Digital Inputs
Digital Input Signals 2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.2 N-m
1.8 lb.-in.
0.2 N-m
1.8 lb.-in.
➌
Digital Outputs
(1)
(1)
Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2)
Applications with ATEX Approved Motors
for more information on installing and configuring the Gate Disable
option board.
Digital Out Relays
2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.5 N-m
4.5 lb.-in.
0.5 N-m
4.5 lb.-in.
I/O Terminal Blocks and Jumpers
➊
➋
J1 & J2
J3 & J4
J5
➌