Table 10.C Frame 13 Power Terminal Specifications
Figure 10.6 Frame 13 Drive Terminal Locations
No. Name
Description
Wire Size Range
(1)(2)
Torque
Terminal Bolt Size
(3)(4)
Maximum
Minimum
Recommended
➊
L1, L2, L3
Input power
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N•m
(354 lb•in)
M12
➋
Output Power Terminal Block
U/T1, V/T2, W/T3
Motor connections
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N•m
(354 lb•in)
M12
➌
SHLD Terminal, PE, Motor Ground
Terminating point for wiring shields 300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N•m
(354 lb•in)
M10
➍
DC Bus
(3 Terminals; DC–, DC+)
DC input or external brake
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N•m
(354 lb•in)
M12
(1)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2)
Do Not exceed maximum wire size. Parallel connections may be required.
(3)
These connections are bus bar type terminations and require the use of lug type connectors.
(4)
Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.
L3
L1
L2
DC-
DC+
DC-
DC+
DC-
DC+
U/T1
V/T2
W/T3
U/T1
V/T2
W/T3
Output Power
Terminals
➊
➍
➌
➋
Right enclosure shown only.