10-14

Frame 13 Installation

Table 10.C Frame 13 Power Terminal Specifications

Figure 10.6 Frame 13 Drive Terminal Locations

No. Name

Description

Wire Size Range

(1)(2)

Torque

Terminal Bolt Size

(3)(4)

Maximum

Minimum

Recommended

Input Power Terminal Block

(1)

L1, L2, L3

Input power

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N•m
(354 lb•in)

M12

Output Power Terminal Block

(3)

U/T1, V/T2, W/T3

Motor connections

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N•m
(354 lb•in)

M12

SHLD Terminal, PE, Motor Ground

(3)

Terminating point for wiring shields 300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N•m
(354 lb•in)

M10

DC Bus

(3)

(3 Terminals; DC–, DC+)

DC input or external brake

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N•m
(354 lb•in)

M12

(1)

Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

(2)

Do Not exceed maximum wire size. Parallel connections may be required.

(3)

These connections are bus bar type terminations and require the use of lug type connectors.

(4)

Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

L3

L1

L2

DC-

DC+

DC-

DC+

DC-

DC+

U/T1

V/T2

W/T3

U/T1

V/T2

W/T3

Output Power

Terminals

Right enclosure shown only.