beautypg.com

Operating temperatures, Operating temperatures -2 – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9-14 Drives Installation - A4 Size User Manual

Page 86

background image

7-2

Frame 10 Installation

Figure 7.2 Enclosure Code B (NEMA/UL Type 1, IP21) and K (NEMA/UL Type 1, IP21
w/Conformal Coat)

Operating Temperatures

Frame 10 drives require a minimum of 2600 m

3

/h (1530 cfm) of cooling air.

200 mm

(7.87 in.) Min.

Powerful Performance, Flexible Control.

838 mm

(33.0 in.) Min.

PowerFlex Drive

Voltage Class

Amp Rating

Surrounding Air Temperature
Normal Duty

Heavy Duty

700H & 700S

400/480V AC
(540/650V DC)

All

0 to 40

°

C

(32 to 104

°

F)

0 to 40

°

C

(32 to 104

°

F)

600/690V AC
(810/932V DC)

261, 325, 385 0 to 40

°

C

(32 to 104

°

F)

0 to 40

°

C

(32 to 104

°

F)

600/690V AC
(810/932V DC)

416

0 to 35

°

C

(32 to 95

°

F)

0 to 40

°

C

(32 to 104

°

F)

This manual is related to the following products: