Control Wiring for PowerFlex 700S Drives with Phase II Control
4-3
I/O Terminal Blocks
Wiring the Main Control Board I/O Terminals
Terminal blocks TB1 and TB2 contain connection points for all inputs,
outputs and standard encoder connections. Both terminal blocks reside on
the Main Control Board.
Remove the terminal block plug from the socket, and make connections.
Important: For NEMA/UL Type 1 applications, all wiring must be routed
through the conduit plate on the drive. Route any wires from the
expanded cassette to the base cassette and out of the drive.
Reinstall the plug when wiring is complete. The terminal blocks have keys,
which make it difficult to insert a terminal plug into the wrong socket.
Table E Control & Encoder Terminal Block Specifications
Name
Description
Wires Size Range
(1)
(1)
Maximum/minimum sizes the terminal block will accept - these are not recommendations.
Main Control Board I/O Terminal Locations
Torque
Maximum
Minimum
Maximum
Recommended
I/O Blocks
Signal & Encoder
power connections
1.5 mm
2
(16 AWG)
0.14 mm
2
(28 AWG)
0.25 N-m
(2.2 lb.-in.)
0.22 N-m
(1.9 lb.-in.)
TB1 Terminals
TB2 Terminals