Control Wiring for PowerFlex 700S Drives with Phase I Control

3-11

Figure 3.3 TB2 - Row T (Top) Wiring Examples

Input/Output

Connection Examples

Required Parameter Changes

Primary Encoder Interface -
Supports 12V dc differential
encoders with internal power
supply.

5V dc differential encoders may
require external power supply
and special jumper settings.
Refer to

Main Control Board I/O

and Encoder Settings on
page 3-17

for external power

supply and jumper settings.

For 5V dc differential encoders
with internal power supply, set
Jumper J6 to positions T2 and
T3.

Primary Encoder - using internal power supply

Example: Using Encoder 0 for Primary Motor
Speed Feedback

Set the value of Parameter 222 [Motor Fdbk
Sel] to a value of 0 - “Encoder 0”, so the drive
will use this encoder as the primary motor
speed feedback device.

Set the value of Parameter 232 [Encoder0 PPR]
to match the encoder’s resolution.

Primary Encoder - using external power supply

13

12

11

10

9

8

7

2

1

Power

Common
(Return)

A

A

B

B

Z

Z

Case Ground

13

12

11

10

9

8

7

Power

Common
(Return)

A

A

B

B

Z

Z

Case Ground

Shield

Power

Common

(Return)