beautypg.com

Rockwell Automation 20D PowerFlex 700H and 700S Frame 9-14 Drives Installation - A4 Size User Manual

Page 66

background image

4-8

Control Wiring for PowerFlex 700S Drives with Phase II Control

0-10V Analog Input

0-10V Analog Input - Bi-Polar

na

0-10V Analog Input

0-10V Analog Input - External Source

Required Parameter Changes
na

Analog Output
+/-10V DC

Used to drive analog
meters displaying speed
and current

0-10V Analog Output

Using Analog Out 1, -10V to + 10V to meter Motor
RPM and direction:

Send the data to the Analog Output
Par 833 [Anlg Out1 Real] (the destination) linked to
Par 71 [Filtered SpdFdbk] (the source)

Scale the Output to the source parameter
Par 835 [Anlg Out1 Scale] = 175 (Par 4 [Motor NP
RPM] = 1750 / 10V)

Using Analog Out 2, -10V to + 10V to meter Motor
Current:

Send the data to the Analog Output
Par 840 [Anlg Out2 Real] (the destination) linked to
Par 308 [Output Current] (the source)

Scale the Output to the source parameter
Par 822 [Anlg Out2 Scale] = xx (Par 2 [Motor NP
FLA] / 10 V Output)