beautypg.com

Power wiring, Power wiring -14 – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9-14 Drives Installation - A4 Size User Manual

Page 128

background image

9-14

Frame 12 Installation

Power Wiring

Input Power Wiring

Frame 12 drives utilize two parallel power structures, and therefore have
two sets of AC input power terminals. You must supply power to both sets
of input terminals. There are several methods for accomplishing this.

Important: Parallel wiring must have the same cable dimensions, type and

routing. Non-symmetrical wiring may cause unequal loading
between the converters and reduce the drive’s ability to deliver
current to the motor.

Figure 9.4 Frame 12 AC Wiring Example: Two Fuses per Phase

1L1

1L2

1L3

2L1

2L2

2L3

L1

L2

L3

AC Input Power Terminals

Inside Drive

AC Input Power Wiring, Fuses, and

Disconnect Device Provided by

Customer