Table 4.A Recommended Control Wire

Type

Wire Type(s)

Description

Insulation
Rating

Digital I/O

Un-shielded Per US NEC or applicable

national or local code

300V, 60

o

C

(140

o

F),

Minimum

Shielded

Multi-conductor shielded cable
such as Belden 8770(or equiv.)

0.750 mm

2

(18AWG), 3

conductor, shielded.

Standard
Analog I/O

Belden 8760/9460(or equiv.)

0.750 mm

2

(18AWG),

twisted pair, 100% shield
with drain

(5)

.

(5)

If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire
may not be necessary, but is always recommended.

300V,
75-90

º

C

(167-194

º

F)

Remote Pot Belden 8770(or equiv.)

0.750 mm

2

(18AWG), 3

cond., shielded

Encoder/
Pulse I/O
Less 30.5 m
(100 ft.)

Combined:

Belden 9730 (or equivalent)

(1)

(1)

Belden 9730 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9728
(or equivalent).

0.196 mm

2

(24AWG),

individually shielded.

Encoder/
Pulse I/O
30.5 m (100
ft.) to 152.4
m (500 ft.)

Signal:

Belden 9730/9728 (or
equivalent)

(1)

0.196 mm

2

(24AWG),

individually shielded.

Power:

Belden 8790

(2)

(2)

Belden 8790 is 1 shielded pair.

0.750 mm

2

(18AWG)

Combined:

Belden 9892

(3)

(3)

Belden 9892 is 3 individually shielded pairs (3 channel), 0.33 mm

2

(22 AWG) plus 1 shielded pair 0.5 mm

2

(20

AWG) for power.

0.330 mm

2

or 0.500 mm

2

(3)

Encoder/
Pulse I/O
152.4 m
(500 ft.) to
259.1 m
(850 ft.)

Signal:

Belden 9730/9728 (or
equivalent)

(1)

0.196 mm

2

(24AWG),

individually shielded.

Power: Belden

8790

(2)

0.750 mm

2

(18AWG)

Combined:

Belden 9773/9774 (or
equivalent)

(4)

(4)

Belden 9773 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9774
(or equivalent).

0.750 mm

2

(18AWG),

individually shielded pair.

EMC
Compliance

Refer to

EMC Instructions on page 1-7

for details.