beautypg.com

Appendix a, Specifications, Allations. refer to – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9-14 Drives Installation - A4 Size User Manual

Page 175: Appendix

background image

Appendix

A

Specifications

Category

PowerFlex 700H

PowerFlex 700S

Agency
Certification

Listed to UL508C and CAN/CSA-C2.2 No. 14-M91.

UL and cUL Listed to UL508C and CAN/CSA - 22.2 No. 14-95.

Marked for all applicable European Directives

(1)

EMC Directive (89/336/EEC)
EN 61800-3 Adjustable Speed electrical power drive systems
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power Installations

Marked for all applicable European Directives
EMC Directive (89/336/EEC)
Emissions:

EN 61800-3 Adjustable Speed electrical power drive systems Part 3

Low Voltage Directive (73/23/EEC)

EN 50178 Electronic Equipment for use in Power Installations

Certified to AS/NZS, 1997 Group 1, Class A.

Certified to AS/NZS, 1997 Group 1, Class A.

Certified to ATEX directive 94/9/EC. Group II Category (2) GD
Applications with ATEX Approved Motors. Refer to Appendix E -

Instructions for ATEX Approved PowerFlex 700H Drives in Group II
Category (2) Applications with ATEX Approved Motors

for more

information.

Certified to ATEX directive 94/9/EC. Group II Category (2) GD Applications
with ATEX Approved Motors. PowerFlex 700S Phase II Control drives only.
Refer to publication 20D-UM006… for more information.

NA

TUV functional safety report only (no FS mark on the label)

The drive is also designed to meet the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 7.1 - Safety standards for Construction and Guide for
Selection, Installation and Operation of Adjustable Speed Drive
Systems.
IEC 146 - International Electrical Code.

The drive is designed to meet applicable requirements of the following
codes/standards:
IEC 61800-2 Adjustable speed electrical power drive systems - General
requirements
IEC 61800-5-1 Adjustable speed electrical power drive systems - Safety
requirements
NFPA 70 - US National Electrical Code

(1)

Applied noise impulses may be counted in addition to the standard pulse train causing erroneously high [Pulse Freq] readings.

N223

II 2 G/D

TUV

Rheinland

Product Safety

.

.

Production inspected

W

E

C

TUV

Rheinland

.

.

Functional

Safety

Bauart geprüft

Type approved

EN 50178

Category

Specification

PowerFlex 700H

PowerFlex 700S

Protection

Drive

380/400V

480V

500V

600V

690V

380/400V

480V

500V

600V

690V

AC Input Overvoltage Trip:

611Vac

611Vac

611Vac

806Vac

806Vac

675Vac

675Vac

675Vac

889Vac

889Vac

AC Input Undervoltage Trip:

235Vac

235Vac

235Vac

326Vac

326Vac

Adjustable

Bus Overvoltage Trip:

911Vdc

911Vdc

911V dc

1200V dc

1200V dc

911Vdc

911Vdc

911Vdc

1200Vdc

1200Vdc

Bus Undervoltage Shutoff/Fault:

333Vdc

333Vdc

333Vdc

461Vdc

461Vdc

Adjustable

Nominal Bus Voltage (Full Load):

517Vdc

621Vdc

645Vdc

776Vdc

890Vdc

540Vdc

648Vdc

645Vdc

810Vdc

931V dc

Heat Sink Thermistor:

Monitored by microprocessor overtemp trip

Monitored by microprocessor overtemp trip

Drive Overcurrent Trip
Software Overcurrent Trip:
Hardware Overcurrent Trip:
Instantaneous Current Limit:


360% of rated Heavy Duty current (typical)

Calculated value, 105% of motor rated to 200% of drive rated
360% of rated Heavy Duty current (typical)

Line transients:

up to 6000 volts peak per IEEE C62.41-1991

Up to 6000 volts peak per IEEE C62.41-1991

Control Logic Noise Immunity:

Showering arc transients up to 1500V peak

Showering arc transients up to 1500V peak

Power Ride-Thru:

15 milliseconds at full load

15 milliseconds at full load

Logic Control Ride-Thru:

0.5 seconds minimum, 2 seconds typical

0.25 seconds, drive not running

Ground Fault Trip:

Phase-to-ground on drive output

Phase-to-ground on drive output

Short Circuit Trip:

Phase-to-phase on drive output

Phase-to-phase on drive output

This manual is related to the following products: