General Installation Information

Essential Requirements for CE Compliance

Conditions 1-6 listed below must be satisfied for PowerFlex drives to meet
the requirements of EN61800-3.

1. Standard PowerFlex 700H or 700S CE compatible Drive. For Frames 10

and up, the drive must also be installed in a suitable Rittal TS 8 (or
equivalent) enclosure.

2. Review important precautions/attention statements throughout this

manual before installing the drive.

3. Grounding as described on

page 1-3

.

4. Output power, control (I/O) and signal wiring must be braided, shielded

cable with a coverage of 75% or better, metal conduit or equivalent
attenuation.

5. All shielded cables should terminate with the proper shielded connector.

6. Conditions in

Table 1.C

.

Table 1.C PowerFlex EN61800-3 EMC Compatibility

Frame

Second Environment
Restrict Motor Cable to 30 m (98 ft.)
Any Drive and Option

9

10

11

12

13

14