Rockwell Automation 20D PowerFlex 700H and 700S Frame 9-14 Drives Installation - A4 Size User Manual
Page 191

Specifications
A-17
Table A.L 690 Volt AC Input Frames 9 - 14 Drive Protection Devices
20xE1K0
13
1100
–
994
1300
(1 per phs)
650
(2 per phs)
2300 1300
(1 per phs)
650
(2 per phs)
3000 170M6466
(5)
3000
1300
–
1000
888
1200
(1 per phs)
600
(2 per phs)
2000
1200
(1 per phs)
600
(2 per phs)
2700
170M6466
(5)
2700
1200
20xE1K1
13
1300
–
1139
1500
(1 per phs)
750
(2 per phs)
2600
1500
(1 per phs)
750
(2 per phs)
3500
170M6466
(5)
3500
1500
–
1100
994
1300
(1 per phs)
650
(2 per phs)
2200
1300
(1 per phs)
650
(2 per phs)
3000
170M6466
(5)
3000
1300
20xE1K5
14
1000
–
1448
1900
(1 per phs)
650
(3 per phs)
3300
1900
(1 per phs)
650
(3 per phs)
4500
170M6466
4500
1900
–
900
1255
1600
(1 per phs)
550
(3 per phs)
2900
1600
(1 per phs)
550
(3 per phs)
3900
170M6466
3900
1700
20xE1K9
(2)
14
1100
–
1834
2300
(1 per phs)
800
(3 per phs)
4200
2300
(1 per phs)
800
(3 per phs)
5700
170M6466
5700
2400
–
1000
1448
1900
(1 per phs)
650
(3 per phs)
3200
1900
(1 per phs)
650
(3 per phs)
4500
170M6466
4500
1900
20xE2K2
(2)
14
1200
–
2172
2800
(1 per phs)
950
(3 per phs)
5000
2800
(1 per phs)
950
(3 per phs)
6700
170M6466
6700
2900
–
1100
1834
2300
(1 per phs)
800
(3 per phs)
4200
2300
(1 per phs)
800
(3 per phs)
5700
170M6466
5700
2400
(1)
20DE820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
(2)
Not available with 700S Control.
(3)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4)
Maximum protection device size is the highest rated device that supplies drive protection.
(5)
These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.
(6)
Inverse time breaker. Ratings shown are maximum.
(7)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(8)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip
settings must be set to US NEC code. Not to exceed 1300% FLA.
Drive
Catalog
Number
Fr
ame HP Rating
Input
Ratings
Dual Element Time Delay
Fuse
Non-Time Delay Fuse
Bussmann Style
Semi-Conductor Fuse
Circuit
Breaker
(6)
Motor Circuit
Protector
(8)
ND
HD
Amps
Min.
(3)
Max.
(4)
Min.
(3)
Max.
(4)
Max
(7)
Max.
Drive
Catalog
Number
Fr
am
e
kW Rating
Input
Ratings
Dual Element Time Delay Fuse
Non-Time Delay Fuse
Bussmann Style
Semi-Conductor Fuse
Circuit
Breaker
(6)
Motor Circuit
Protector
(8)
ND
HD
Amps
Min.
(3)
Max.
(4)
Min.
(3)
Max.
(4)
Max.
(7)
Max.
20xF170
9
160
–
171
225
375
225
500
170M3819
500
250
–
132
145
200
300
200
500
170M3819
400
200
20xF208
9
200
–
210
275
450
275
600
170M3819
600
300
–
160
171
225
375
225
500
170M3819
500
250
20xF261
10
250
–
263
350
575
350
775
170M5813
750
350
–
200
210
275
450
275
600
170M5813
600
300
20xF325
10
315
–
327
425
725
425
950
170M5813
900
450
–
250
263
350
575
350
775
170M5813
750
400
20xF385
10
355
–
388
500
850
500
1100
170M5813
1100
500
–
315
327
425
725
425
950
170M5813
900
450
20xF416
10
400
–
419
525
900
525
1200
170M5813
1200
550
–
315
327
425
700
425
950
170M5813
900
450
20xF460
11
500
–
463
600
(1 per phs)
300
(2 per phs)
1000
600
(1 per phs)
300
(2 per phs)
1300
170M8547
1300
600
–
400
388
500
(1 per phs)
250
(2 per phs)
850
500
(1 per phs)
250
(2 per phs)
1100
170M8547
1100
500
20xF502
11
560
–
506
650
(1 per phs)
325
(2 per phs)
1100
650
(1 per phs)
325
(2 per phs)
1500
170M8547
1500
650
–
500
463
600
(1 per phs)
300
(2 per phs)
1000
600
(1 per phs)
300
(2 per phs)
1300
170M8547
1300
600
20xF590
11
580
–
594
750
(1 per phs)
375
(2 per phs)
1300
750
(1 per phs)
375
(2 per phs)
1700
170M5813
1700
800
–
500
506
650
(1 per phs)
325
(2 per phs)
1100
650
(1 per phs)
325
(2 per phs)
1500
170M5813
1500
700