Installation and Hookup

4-35

Publication 999-122 - January 1997

AxisLink Settings for Extended Length AxisLink Operation

Switch 1 (SW1) on the AxisLink board must be set to the EXTENDED
setting (away from the edge of the board).

Jumper 5 (J5), labeled XTEND on the board, must be in place across
both J5 pins if using onboard cable termination. Jumper 6 (J6) on the
board should not be connected.

If you are not using the onboard termination resistors, both jumper 5
(J5) and 6 (J6) should not be in place across the pins on the board.

To connect the AxisLink option, remove the 3 terminal pluggable
terminal block from the AxisLink connector and connect the AxisLink
cable to it as shown below. If this IMC-S/23x is either the first or the
last physical module on the AxisLink cable and the onboard cable
termination resistors are not used, also connect a terminating resistor.

Standard Configuration Diagram

XTEND

STD

J6

EXTENDED

SW1

J5

AxisLink Terminal

Block

*

Install termination resistor

only if this

is the first or last physical module on
the AxisLink

and if the onboard cable

termination resistors are not used.

A-B 1770-CD
(Belden 9463 or
Equivalent)

*150

Standard AxisLink Cable