beautypg.com

Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 65

background image

3-49

M-4659

Configuring the DX1000/DX2000

1

2

3

4

5

6

7

8

Index

Serial

For RS-232
• Baud Rate

Select 1200, 2400, 4800, 9600, 19200, or 38400 (bps).

• Parity

Set the parity check method to Odd, Even, or None.

• Data length

Select 7 or 8 (bits). To output the data in binary format, select 8.

• Handshaking

Select Off:Off, XON:XON, XON:RS, or CS:RS.

• Address

For Modbus protocol, enter a value in the range of 1 to 99. For a general purpose

communication protocol, this value is not set.

• Protocol

Select [Normal] for a general purpose communication protocol, [MODBUS] for Modbus

slave, and [Master] for Modbus master.

If Modbus master is selected, Modbus master settings must be entered.

For RS-422/485
• Baud rate

Select 1200, 2400, 4800, 9600, 19200, or 38400 (bps).

• Data length

Select 7 or 8 (bits). To output the data in binary format, select 8.

• Parity

Set the parity check method to Odd, Even, or None.

• Handshaking

Not specified.

• Address

Select a number from 1 to 99.

• Protocol

This is the same as with the RS-232.

3.6 Entering Basic Settings