beautypg.com

Index – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 45

background image

3-29

M-4659

Configuring the DX1000/DX2000

1

2

3

4

5

6

7

8

Index

• Service port

The following table indicates the number of simultaneous uses (number of users that

can use the function simultaneously), the maximum number of connections, and the
port number for each function.

Function

Maximum
Number of
Connections

Number of Simultaneous Uses

Port No.

Administrator

User

FTP server

2

2

2

*1

21/tcp

*3

Web server (HTTP)

1

80/tcp

*3

SNTP server

123/udp

*3

Modbus server

2

502/tcp

*3

Instrument
information server

34264/udp

*2

*1 There are user limitations. For details, see the DX1000/DX1000N/DX2000 Communication

interface User’s Manual (IM04L41B01-01E).

*2 The port number is fixed.
*3 The default port number. You can set the value in the range of 1 to 65535. Use the default

port number unless there is a special reason not to do so.

• Status Relay

If an abnormality occurs with items turned ON, relay contact output is performed. In

the [System Configuration] screen, if [FAIL] is set to [FAIL/Alarm relay] (/F2 option) or
[FAIL/Status relay] (/F1 option), the [Status Relay] setting items are displayed.

Detail Setting

• Tag

Settings

Description

Tag

Displays tags. Channel numbers are displayed for channels that do not
have tags assigned.

Channel

Displays channel numbers.

• Language

Select the display language

• Remote controller ID

Select the remote controller ID from 0 to 31. When not using the remote control

terminal, select [OFF].

• Batch

Select [ON] to use the batch function.

• Digit of lot number

Select the number of digits of the lot number from 4, 6, or 8. Select [OFF] to disable

the lot number.

3.6 Entering Basic Settings