• Auto Save

Settings

Description

ON

Automatically saves the measured data to the CF card.

OFF

Does not automatically save the data. Save the measured data manually to
the CF card or USB flash memory (/USB1 option).

• Media FIFO

You can select this with MV main unit firmware version 2.0x or later.
This is valid only when [Auto Save] is [ON].

Settings

Description

ON

If there is no more free space on the CF card, the oldest file is deleted, and
the newest file is saved.

OFF

If there is no more free space on the CF card, the measured data is not saved
to the CF card.

Option

• Value on Error

Specify whether to set the display for a computation error to [+Over] or [–Over].

• Overflow Sum, Ave

Specify how to handle overflow data when it is detected in the SUM or AVE

computation of TLOG or CLOG. This setting is also applied to report generation.

Settings

Description

Error

Sets the computed result to computation error.

Skip

Discards the overflow data and continues the computation.

Limit

Uses a limit value in place of the overflow data and continues the
computation.

• Overflow Min, Max, P-P

Specify how to handle overflow data when it is detected in the MAX, MIN, or P-P

computation of TLOG or CLOG. This setting is also applied to report generation.

Settings

Description

Over

Uses the overflow data as-is.

Skip

Discards the overflow data and continues the computation.

• Report (1 to 4)

Select the type of data to output as reports.

Settings

Description

OFF

Does not output reports. You cannot set the first term to [OFF].

Ave

Outputs the average value.

Max

Outputs the maximum value.

Min

Outputs the minimum value.

Sum

Outputs the sum value.

Instant

Outputs the instantaneous value.

6.6 Entering Basic Settings