Configuring the CX1000/CX2000

Rate of Change Increase
Select the number of data samples that determines the interval of the rate of change of
an upper limit alarm between [1] and [15].

Rate of Change Decrease
Select the number of data samples that determines the interval of the rate of change of a
lower limit alarm between [1] and [15].

Alarm Hysteresis
Set the alarm hysteresis to [ON] or [OFF]. When it is [ON], the hysteresis is set to 0.5%
of the scale or the measurement span.

Remote (Option)

You can assign items to be controlled by the eight remote control terminals. This setting
is available with the measurement remote input function. For details, refer to the CX
User’s Manual (IM 04L31A01-01E or IM 04L31A01-03E)
.
Select a remote number, and then click the [Copy] button. This copies the setting of that
remote number. When you want to paste the copied setting, select the remote number
where you want to paste the setting, and then click the [Paste] button.

Scan Interval/Memory

Set these parameters when the data type is [EVENT & DISP] or [EVENT].

Click here. (Or choose the [Setting] menu - [SETUP [Basic] Setting] - [Setting].)

Select the channels that

you want to sample.

A/D Integrate

Select from [Auto], [50 Hz], [60 Hz], and [100 ms]. The [Auto] setting automatically
detects the CX power supply frequency, and switches the integration time.

Scan Interval

Select [1s] or [2s].

7.7 Basic Measurement Function Basic Settings