Measure Function

Burnout

Settings

Description

OFF

Sensor disconnections are not detected.

UP

When the sensor burns out, the measured result is set to +over range. The
measured value displays “Burnout.”
For 1-5V input, the MV assumes that the sensor has burned out when the
measured value exceeds the scale upper limit by 10% of the scale width.
(Example: When the measured value is greater than 110 when the scale is
from 0 to 100)

DOWN

When the sensor burns out, the measured result is set to –over range. The
measured value displays “Burnout.”
For 1-5V input, the MV assumes that the sensor has burned out when the
measured value falls below the scale lower limit by 5% of the scale width.
(Example: When the measured value is less than –5 when the scale is from 0
to 100)

RJC Mode

Sets the reference junction compensation method of the thermocouple input. Select
[Internal] or [External].

Settings

Description

Internal

Uses the reference junction compensation function of the MV.

External

Uses an external reference junction compensation function. When set to
[External], [Volt] is displayed.

RJC voltage (µV)

The compensation voltage to be added to the input. Set the value in the range of
–20000 µV to 20000 µV.