Configuring the CX1000/CX2000

Partial

Expand(%)
The boundary value is displayed as a percentage along the width of the display, between
1 and 99%.

Boundary
The setting conditions depend on the internal control channel and external control
channel as follows:
• Internal control channel
PV /SP: EU (0%) < boundary value < EU (100%)
OUT: EU (-5.0%) < boundary value < EU (105.0%)
However, with OUT for analog retransmission, minimum value of span < boundary

value < maximum value of span.

• External control channel
span L + 1 digit < boundary value < span U - 1 digit
However, when external loop is OFF, the partial expansion/reduction is also OFF.

Note

• The partial expansion/reduction settings are valid when [Partial] is set to [Use] in [Aux] of the

[Setup] tab.

• For the external control channel, set a boundary within the span determined by the internal

span -50–1050 and the specified decimal point. Normally there is one decimal place, so it
can be set to -5.0% < boundary < 105.0%.

Color

Click in the display color setting field to display a color selection dialog box.
You can select the display color of each channel from 16 colors.

7.5 Control Channel Settings (Internal/External)