7-36
M-4659
Start code
Select the operation start condition from the following. Note that only the possible loop
conditions are displayed.
Starting target setpoint start, PV1 to PV 6 ramp-prioritized PV start, time-prioritized ramp
start (not displayed for segment time ramp setting method).
Wait action setting
Set the wait zones for 6 (number of loops) × 5 (number of zones) (CX1000: 2 (number of
loops) × 5 (number of zones))in the range of [EUS (0.0 to 100.0%)] of the measurement
span. For style 3 or later, the wait action setting for loops turned ON in operating loop
designation can be entered. With style 2 or earlier, settings for loops turned ON in
Program Control under Internal Loops in the Setup tab can be entered.
Wait time
Set the wait time in [hh:mm:ss] format (selectable range: [00:00:00] to [99:59:59]) for
all the available zones. The setting applies to the same zones in each loop. Wait time
cannot be set if the wait zone for all loops is set to OFF.
Operating Loop Designation
Set the loops to operate.
Select from loops whose program control is ON.
7.6 Program Control Related Setup Operations