Index

Configuring the CX1000/CX2000

Initial Program Patterns

You can set the initial program patterns. You can set the initial (default) program patterns
by clicking the [Program pattern] tab, then selecting [Default setting]. Settings cannot be
entered when the number of segments is 0. Add segments using [Segment setting].

Set the start code

Available when segments have been inserted or added under [Segment setting].

Set the start setpoint

Available when segments have been inserted or added under [Segment setting].

Copy the settings (Default setting/Segment setting)

Paste copied pattern settings (Default setting/Segment setting)

Select the pattern number

Pattern Default setting

Pattern name, Setting method, Start setpoint, Start code

Enter a pattern name setting

Segment setting

Program pattern, PV Event, Time Event, Repeat

Event output setting

AUX setting

Automatic message printout, program display position

Event display group setting

Click this tab

Segment and event totals

(cannot be set here)

The number of segments

and events used with

this pattern.

(cannot be set here)

Set the segment setting

method

Zone number

Wait setting

Available when segments

have been inserted or

added under

[Segment setting].

Wait time setting

PV event hysteresis settings

Set the operating loop

Pattern number

Select the number of the desired pattern from [1] to [30] ([1] to [4] for models with /PG1
option).

Pattern name

Enter the pattern name using up to 16 alphanumeric characters.

Segment setting method

Select segment time setting method or segment time ramp grade setting method. If you
change this setting, the program pattern setting corresponding to the pattern number is
initialized.

Start target setpoint

Set the start SP, a starting condition, in the range of [EU (0.0% to 100.0%)] (initial value
is 0%) of the measurement span. For style 3 or later, the PV event hysteresis setting for
loops turned ON in operating loop designation can be entered. With style 2 or earlier,
settings for loops turned ON in Program Control under Internal Loops in the Setup tab
can be entered. Only the loops that are set as follows are displayed: [Setup] tab > [Internal
Loop] > [Program control] to [On]. During cascade control, even-numbered loops within
the same terminal block are not displayed.

7.6 Program Control Related Setup Operations