Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 63
3-47
M-4659
Configuring the DX1000/DX2000
1
2
3
4
5
6
7
8
Index
Report
Specify the settings for sending e-mail when reports are created.
• Recipient1 and Recipient2
Set the recipients. For Recipient1 and Recipient2, select On to send e-mail or OFF to
not send e-mail.
• Include source URL, Subject, and Header
These items are the same as the e-mail that is sent when an alarm occurs. The
default subject is Report_data.
SNTP Client
• Use
Select [Use] to use the SNTP client function; Otherwise, select [Not]. If you select [Use],
the SNTP client settings are displayed.
• Server Name
Set the SNTP server name using up to 64 alphanumeric characters.
• If the DNS is used, you can set the host name as a server name.
• You can also set the IP address. In this case, the DNS is not required.
• Port No.
Enter the port number of the file transfer destination SNTP server in the range of 1 to
65535. The default value is 123.
• Access Interval
Set the time interval for synchronizing the time with the server to OFF, 1, 8, 12, or 24h.
If you select OFF, you can synchronize the time manually by operating soft keys. The
time is not synchronized if the difference in the time between the DX and the server is
greater than or equal to 10 minutes.
• Ref. Time
Set the reference time for making queries.
• Access timeout
Set the time to wait for the response from the SNTP server when querying the time to
10, 30, 90s.
• Time adjust (start)
Select [On] to synchronize the time using SNTP when memory start is executed;
Otherwise, select [OFF].
3.6 Entering Basic Settings