M-4659

Configuring the MV1000/MV2000

1

2

3

4

5

6

7

8

Index

Relay hold

Select the alarm output relay behavior from below: The setting applies to all relays.

Settings

Description

Unhold

Turns the output relay OFF when the alarm condition is released (returns to
normal condition).

Hold

Holds the output relay at ON until an alarm acknowledge operation is performed.

Relay Action on ACK
You can select this with MV main unit firmware version 2.0x or later.

Settings

Description

Normal

The relay output is deactivated when the alarm ACK operation is executed. If the
condition for activating the alarm output relay is met in the next scan interval, the
relay output is activated.
This operation is valid only when the alarm output relay is set to [Hold].

Reset

The relay output is deactivated when the alarm ACK operation is executed. If a
new condition for activating the alarm output relay, the relay is activated.

Note

When reflash is turned ON, the operation of the first three output relays is set to nonhold.
Specifying Hold produces no effect.

Measure channel High/Low

Sets the hysteresis width of the alarm occurrence/release of the high/low limit alarm
specified on measurement channels.
Selectable range: 0.0% to 5.0% of the span or scaling width

Measure channel Delta High/Low

Sets the hysteresis width of the alarm occurrence/release of the difference high/low limit
alarm specified on measurement channels.
Selectable range: 0.0% to 5.0% of the span

Math channel High/Low, Ext channel High/Low

Sets the hysteresis width of the alarm occurrence/release of the high/low limit alarm
specified on computation and external input channels.
Selectable range: 0.0% to 5.0% of the measurement span

Scan Interval

Scan interval
Select a scan interval.
A/D integrate

Select the A/D integration time as necessary. Only the selectable settings are displayed.

Settings

Description

Auto

The MV automatically detects the power supply frequency and sets the integration
time to 16.7 ms and 20 ms for 60 Hz and 50 Hz, respectively. Fixed to 20 ms on /
P1 models that use the 24 VDC power supply.

50Hz

Sets the integration time to 20 ms.

60Hz

Sets the integration time to 16.7 ms.

100ms

Sets the integration time to 100 ms (when the scan interval is 2 s or 5 s).

600Hz

The A/D integration time for fast sampling mode. You cannot change this value.
You cannot use fast sampling mode on models with the external input channel (/
MC1) option.

6.6 Entering Basic Settings