Configuring the CX1000/CX2000
Filter (PV1, Remote)
Select the check box to turn the filter, ON/OFF.
When it is ON, set between 1s and 120s.
[Linearizer] tab
Mode
Select the linearize mode from [OFF], [Biasing], or [Approximation].
Input
Enter the linearize input value. (The value depends on the linearize mode.)
Biasing: Set with measurement input span EU (–5.0 to 105.0%).
Approximation: Set with measurement input span EU (–5.0 to 105.0%).
Set between 2 and 11 points.
Output
Enter the linearize output value. (The value depends on the linearize mode.)
Biasing: Set with measurement input span EUS (–100.0 to 100.0%).
Approximation: Set with measurement input span EU (–5.0 to 105.0%).
Note
• With linearize bias, set so that input + output is EU (0-100%). Also, set so that linearizer
input + linearizer output is greater than or equal to the previous linearizer input + linearizer
output.
• Set so that linearizer approximation output is more than the previous value.
• Starting from the third point, if you set a value smaller than the previous value, all settings
after that point become disabled.
• When the PV/SP computation function is OFF, the above settings are entered for each loop
item on the Setting tab. See page 7-25 for the setting method.
7.4 Control Function General Settings