beautypg.com

Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 205

background image

7-31

M-4659

1

2

3

4

5

6

7

8

Index

Configuring the CX1000/CX2000

Filter (PV1, Remote)
Select the check box to turn the filter, ON/OFF.
When it is ON, set between 1s and 120s.

[Linearizer] tab

Mode
Select the linearize mode from [OFF], [Biasing], or [Approximation].

Input
Enter the linearize input value. (The value depends on the linearize mode.)

Biasing: Set with measurement input span EU (–5.0 to 105.0%).
Approximation: Set with measurement input span EU (–5.0 to 105.0%).
Set between 2 and 11 points.

Output
Enter the linearize output value. (The value depends on the linearize mode.)

Biasing: Set with measurement input span EUS (–100.0 to 100.0%).
Approximation: Set with measurement input span EU (–5.0 to 105.0%).

Note

• With linearize bias, set so that input + output is EU (0-100%). Also, set so that linearizer

input + linearizer output is greater than or equal to the previous linearizer input + linearizer
output.

• Set so that linearizer approximation output is more than the previous value.
• Starting from the third point, if you set a value smaller than the previous value, all settings

after that point become disabled.

• When the PV/SP computation function is OFF, the above settings are entered for each loop

item on the Setting tab. See page 7-25 for the setting method.

7.4 Control Function General Settings