dix
(In the panel window, the three digits after “E” indicate an error number.)
Error No.
Error name
Description, action, etc.
D50
Fieldbus error (FBMIRQ timeout)
A FBMIRQ timeout was detected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D51
Fieldbus error (FBMIRQ reset)
A FBMIRQ reset error was detected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D52
Fieldbus error (FBMBSY)
A FBMBSY was detected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D53
Fieldbus error (BSYERR)
A BSYERR was detected. The power must be reconnected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D54
Window lock error (LERR)
A LERR was detected. The power must be reconnected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D55
Fieldbus error (Min busy)
A Min busy error was detected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D56
Fieldbus error (MinACK timeout)
A Min ACK timeout was detected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D57
Fieldbus error (MoutSTB timeout)
A Mout STB timeout was detected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D58
Fieldbus error (INIT timeout)
An INIT timeout was detected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D59
Fieldbus error (DPRAM write/read)
A DPRAM write/read error was detected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D5A
Fieldbus error (TOGGLE timeout)
A TOGGLE timeout was detected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D5B
Fieldbus error (Access-privilege retry over)
An access-privilege retry over error was detected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.
D5C
Fieldbus error (Access-privilege open error)
An access-privilege open error was detected.
Check the status of the monitor LED on the front face of the board by referring to
the operation manual for the field network board.