Other parameters, 422 appendix – IAI America PSEL User Manual
Page 432

422
Appendix
7. Other
Parameters
No. Parameter
name
Default value
(Reference)
Input range
Unit
Remarks
1 Auto-start
program
number
0
0 ~ 64
(Invalid if “0” is set)
2 I/O
processing
program
number at
operation/program abort
0
0 ~ 64
The start trigger is determined from the “I/O processing
program start type at operation/program abort.” (Note: This
program will be started before confirming an abort of other
programs.)
(Invalid if “0” is set) * If the setting is valid, the number of user
program tasks that can be used will decrease by 1.
3 I/O
processing
program
number at all operation
pause
0
0 ~ 64
This program will be started when an all-operation-pause
command is issued due to an all-operation-pause factor. (Only
when a program is running) (Invalid if “0” is set) * If the setting
is valid, the number of user program tasks that can be used will
decrease by 1.
4
Program abort type at
error
0
0 ~ 5
0: Cancel only the program in which an error of
operation-cancellation level or higher has generated. (If the
error requires the drive source to be cut off or a servo-OFF
or all-axis servo-OFF request to be issued, all programs
other than the “I/O processing program at
operation/program abort” will be cancelled.)
1: Cancel all programs other than the “I/O processing program
at operation/program abort” when an error of
operation-cancellation level or higher has generated.
5 I/O
processing
program
start type at
operation/program abort
0
0 ~ 5
0: When all-operation-cancellation factor has generated (Only
when a program is running)
1: When all-operation-cancellation factor has generated
(Always)
2: All-operation-cancellation factor + Error of
operation-cancellation level or higher (“Other parameter No.
4 = 0” is considered) (Only when a program is running)
3: All-operation-cancellation factor + Error of
operation-cancellation level or higher (“Other parameter No.
4 = 0” is considered) (Always)
6 PC/TP
reconnection
delay
at software reset
14000
1 ~ 99999
msec
* The setting will become effective after the controller, PC or
TP is restarted.
7
Auto program start setting
1
0 ~ 5
0: Do not start the auto-start program upon power ON
reset/software reset
1: Start the auto-start program
8 (For
expansion)
0
9 For
future
expansion
(change prohibited)
0 0
~
2
10 Emergency-stop
recovery
type
0
0 ~ 4
0: Abort operations/programs
1: Recovery after reset
2: Operation continued (Only during automatic operation.
* Operation commands from the PC/TP will be aborted on
the PC/TP side.)
3: Abort operations/programs (Software reset when the
emergency stop is reset. The home-return completion
status of incremental-encoder axes will be reset (EG
approximation swap).)
4: Abort operations/programs (Error reset (only with an error
of operation-cancellation level or lower) and auto-start
program start (only if AUTO mode AND other parameter
No. 7 = 1 AND I/O parameter “Input function selection”
17
AND all-operation-cancellation factor is not present) when
the emergency stop is reset.
There must be a minimum interval of 1 second after an
emergency stop is actuated before it is reset. The
home-return completion status of incremental-encoder axes
will be retained.
11 Enable
switch
(deadman/enable switch)
recovery type
0
0 ~ 2
0: Abort operations/programs
1: Recovery after reset
2: Operation continued (Only during automatic operation.
* Operation commands from the PC/TP will be aborted on
the PC/TP side.)