Application and Configuration Examples
8-15
16. Choose
Close
to exit the Drive Parameters window.
17. Verify the Status indicator is green.
18. Select the
I/O
C
onfiguration
command icon from the Drive Win-
dow.
19. Select an appropriate digital input from the pull-down lists avail-
able as Digital Input Assignments in the I/O Configuration win-
dow.
For example:
•
Follower Enable
as Input 1
•
Not Assigned
as Inputs 2 through 4.
•
Not Assigned
as Outputs 1 through 4.
20. Choose
Close
to exit the I/O Configuration window.
Tuning
1. Choose the
Tuning
command icon from the Drive window.
2. Select
A
utoTune
from the Tuning mode group.
3. Select the appropriate values for the following Auto Tune com-
mands:
•
Distance
and
• Step Current.
4. Select the appropriate entry for the Motor Direction:
•
BiDirectional
,
•
Forward Only
or
•
Reverse Only.
5. Close the toggle switch between J1-26 and J1-20 to enable the
drive.
6. Choose
S
tart
from the Tuning window. The drive powers the
motor shaft for a short period and then motion will cease. Then
ULTRA Master displays the calculated gains and disables the
drive.
Note: Do not attempt to Auto Tune systems that have gravitational
effects. The ULTRA 200 Series will not hold initial position.
!
Intro
ATTENTION: Rotating motor shafts can cause extensive
damage and injury. Motors must be properly guarded dur-
ing testing and installation.