Connection diagram, Configuration, Preset controller connection diagram – Rockwell Automation 1398-DDM-xxx USE MNL/ULTRA 200 DIG.SERVO.DR User Manual
Page 132: Connection diagram configuration
Publication 1398-5.0 – October 1998
8-8
Application and Configuration Examples
Connection Diagram
Configuration
Carefully check all connections before entering these parameters.
1. Switch the AC Power to ON and verify:
• green DC BUS LED is ON
• display shows an operational status: A, F or P (Analog, Fol-
lower or Preset mode of operation). Refer to “Operating Mes-
sages” on page 10-1 for an explanation of the display codes.
2. Start ULTRA Master on the PC.
3. Choose
Cancel
from the Drive Select dialog box.
4. Select
P
C Set Up
from the Communications menu in
ULTRA Master to display the personal computer’s communica-
tion settings
5. Verify the communications port settings of the PC match those of
the drive.
• If the settings are correct, select
OK
in the Port – Settings dia-
log box.
Figure 8.2
Preset Controller Connection Diagram
Intro
J1
26 +24V
20 ENABLE
21 FAULT
32 INPUT1
33 INPUT2
Close to ENABLE Drive
Close to RESET Fault
34 INPUT3
Close to Turn ON
Close to Turn ON
Close to Turn ON
DRIVE
TB1
L1
L2/N
Gnd
L1
L2/N
Gnd
100-240 VAC
50/60 Hz
Three Phase
Power Source
L3
or
100-240 VAC
50/50 Hz
Single Phase
Power Source
TB1
J4
2 RCV
3 XMT
5 COM
XMT
RCV
COM
RESET
TB1
Phase R 1
Phase S 2
Phase T 3
Motor Gnd 4
J2
Motor
Encoder