Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 96
3-42
Programming and Parameters
304
Limit Status
Displays the limit status of conditions that may be limiting the current reference or torque reference.
• Bit 0 [+MCS Iq Lim] indicates that torque producing current is at its positive limit.
• Bit 1 [+MCS Ws Lim] indicates that flux producing torque is at its positive limit.
• Bit 2 [0 Ia from +] indicates that torque producing current is limited to zero from the positive direction - refer to Par 353 [Iq Actual Lim].
• Bit 3 [+Iq Calc] indicates the calculation for torque producing current has reached its positive limit.
• Bit 4 [+Current Lim] indicates that the current reference has reached the positive Motor Current Limit set by Par 356 [Mtr Current Lim].
• Bit 5 [+DriveProtOL] indicates that the current reference has reached the positive current limit set by the Open Loop Inverter Overload, shown in Par 343 [OL
OpnLp CurrLim].
• Bit 6 [+DriveProtCL] indicates that the current reference has reached the positive current limit set by the Closed Loop Inverter Overload, shown in Par 344
[OL ClsLp CurrLim].
• Bit 8 [+Torq Limit] indicates that the torque reference has reached the Positive Torque Limit set by Par 125 [Torque Pos Limit].
• Bit 9 [Mtrng PwrLim] indicates that the torque reference is being limited by the Motoring Power Limit set by Par 127 [Mtring Power Lim].
• Bit 10 [+Torq CurLim] indicates that current reference has reached the Actual Torque Producing Current Limit set by Par 353 [Iq Actual Lim].
• Bit 11 [Atune Tq Lim] indicates that the torque reference is being limited by Par 129 [Atune Torq Ref].
• Bit 12 [+0 Torq Ena] indicates that the torque reference is limited to zero because Par 157 [Logic Ctrl State] bit 9 [Torq Ref En] is off.
• Bit 13 [+0 Curr Ena] indicates that the current reference is limited to zero because Par 157 [Logic Ctrl State] bit 11 [CurrRef En] is off.
• Bit 16 [-MCS Iq Lim] indicates that torque producing current is at its negative limit.
• Bit 17 [-MCS Ws Lim] indicates that flux producing torque is at its negative limit.
• Bit 18 [0 Iq from -] indicates that torque producing current is limited to zero from the negative direction - refer to Par 353 [Iq Actual Lim].1
• Bit 19 [-Iq Calc] indicates the calculation for torque producing current has reached its negative limit.
• Bit 20 [-Current Lim] indicates that the current reference has reached the negative Motor Current Limit set by Par 356 [Mtr Current Lim].
• Bit 21 [-DriveProtOL] indicates that the current reference has reached the negative current limit set by the Open Loop Inverter Overload, shown in Par 343
[OL OpnLp CurrLim].
• Bit 22 [-DriveProtCL] indicates that the current reference has reached the negative current limit set by the Closed Loop Inverter Overload, shown in Par 344
[OL ClsLp CurrLim].
• Bit 24 [-Torq Limit] indicates that the torque reference has reached the Negative Torque Limit set by Par 126 [Torque Neg Limit].
• Bit 25 [Regen PwrLim] indicates that the torque reference is being limited by the Regenerative Power Limit set by Par 128 [Regen Power Lim].
• Bit 26 [-Torq CurLim] indicates that current reference has reached the Actual Torque Producing Current Limit set by Par 353 [Iq Actual Lim].
• Bit 27 [Bus Reg Tq Lim] indicates the bus voltage regulator is active and limiting the regenerative torque.
• Bit 28 [-0 Torq Ena] indicates that the torque reference is limited to zero because Par 157 [Logic Ctrl State] bit 9 [Torq Ref En] is off.
• Bit 29 [-0 Curr Ena] indicates that the current reference is limited to zero because Par 157 [Logic Ctrl State] bit 11 [CurrRef En] is off.
305
Mtr TorqCurr Ref
Displays the torque current reference present at the output of the current rate limiter.
100% is equal to 1 per unit (pu) rated motor torque.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
Real
306
DC Bus Voltage
Displays measured bus voltage.
Units:
Default:
Min/Max:
Volt
0.0000
0.0000/1000.0000
Real
307
Output Voltage
Displays RMS line-to-line fundamental motor voltage. This data is averaged and updated
every 50 milliseconds.
Units:
Default:
Min/Max:
Volt
0.00
0.00/3000.00
Real
308
Output Current
Displays measured RMS motor current.
Units:
Default:
Min/Max:
Amps
0.00
0.00/10000.00
Real
309
% Motor Flux
Displays the motor flux in % of nominal.
Units:
Default:
Min/Max:
Comm Scale:
%
100.0
0.0/100.0
100 = 4096
16-bit
Integer
310
Output Freq
Displays the motor stator frequency.
Units:
Default:
Min/Max:
Hz
0.00
-/+250.00
Real
311
Output Power
Motor Power is the calculated product of the torque reference and motor speed feedback.
A 125mS filter is applied to this result. Positive values indicate motoring power; negative
values indicate regenerative power.
Units:
Default:
Min/Max:
Hp
0.00
-/+9999.00
Real
312
MotorFluxCurr FB
Displays the measured per unit motor flux producing current.
Units:
Default:
Min/Max::
P.U.
0.0000
0.0000/1.0000
Real
No.
Name
Description
Values
Li
nkab
le
Read
-Wr
it
e
Da
ta
T
ype
Options
Reser
ved
Reser
ved
-0
Cu
rr
Ena
-0
T
orq
En
a
Bus Reg Lim
-T
or
q Cur
Li
m
Regen
Pwr
Lim
-T
or
q Lim
-Sp
dReg Open
-Dr
iv
eProtCL
-Dr
iv
ePr
ot
OL
-C
ur
re
nt
Li
m
-I
q Cal
c
0
Iq
fr
om -
-MCS Ws Lim
-MCS Iq
Li
m
Reser
ved
Reser
ved
+0
Cu
rr
En
a
+0
T
orq
En
a
Atu
ne Tq Lim
+T
or
q Cur
Lim
Mtr
ng Pwr
Lim
+T
or
q Limit
+SpdRe
g Op
en
+Dr
iv
eProtC
L
+Dr
iv
eProtOL
+Cur
re
nt Lim
+Iq
Ca
lc
0
Iq
fr
om +
+MCS W
s
Li
m
+MCS Iq Lim
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True