Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 25
Installation/Wiring
1-11
Table 1.D Power Terminal Block Specifications
No. Name
Frame
Description
Wire Size Range
(1)
Torque
Terminal Bolt Size
(2)
Maximum
Minimum
Maximum
Recommended
➊
Power Terminal Block 1
Input power and motor
connections
4.0 mm
2
(10 AWG)
0.5 mm
2
(22 AWG)
1.7 N-m
(15 lb.-in.)
0.8 N-m
(7 lb.-in.)
—
2
Input power and motor
connections
10.0 mm
2
(6 AWG)
0.8 mm
2
(18 AWG)
1.7 N-m
(15 lb.-in.)
1.4 N-m
(12 lb.-in.)
—
3
Input power and motor
connections
25.0 mm
2
(3 AWG)
2.5 mm
2
(14 AWG)
3.6 N-m
(32 lb.-in.)
1.8 N-m
(16 lb.-in.)
—
BR1, BR2
10.0 mm
2
(6 AWG)
0.8 mm
2
(18 AWG)
1.7 N-m
(15 lb.-in.)
1.4 N-m
(12 lb.-in.)
—
4
Input power and motor
connections
35.0 mm
2
(1/0 AWG)
10 mm
2
(8 AWG)
4.0 N-m
(24 lb.-in.)
4.0 N-m
(24 lb.-in.)
—
5
(75 HP)
(3)
R, S, T, BR1, BR2, DC+,
DC-, U, V and W
50.0 mm
2
(1/0 AWG)
2.5 mm
2
(14 AWG)
See Note
(4)
See Note
—
PE
50.0 mm
2
(1/0 AWG)
4.0 mm
2
(12 AWG)
—
5
(100 HP)
R, S, T, DC+, DC-, U, V and
W
70.0 mm
2
(2/0 AWG)
16.0 mm
2
(6 AWG)
—
BR1, BR2
50.0 mm
2
(1/0 AWG)
2.5 mm
2
(14 AWG)
—
PE
50.0 mm
2
(1/0 AWG)
4.0 mm
2
(12 AWG)
—
6
Input power and motor
connections
120.0 mm
2
(4/0 AWG)
2.5 mm
2
(14 AWG)
6 N-m
(52 lb.-in.)
6 N-m
(52 lb.-in.)
—
➋
SHLD Terminal
1-6
Terminating point for wiring
shields
—
—
1.6 N-m
(14 lb.-in.)
1.6 N-m
(14 lb.-in.)
M12
➌
AUX Terminal Block
1-4
Auxiliary Control Voltage
(5)
PS+, PS-
1.5 mm
2
(16 AWG)
0.2 mm
2
(24 AWG)
—
—
—
5-6
4.0 mm
2
(10 AWG)
0.5 mm
2
(22 AWG)
0.6 N-m
(5.3 lb.-in.)
0.6 N-m
(5.3 lb.-in.)
—
➍
Fan Terminal Block
(Common Bus Only)
5-6
User Supplied Fan Voltage
0V AC, 120V AC, 240V AC
4.0 mm
2
(10 AWG)
0.5 mm
2
(22 AWG)
0.6 N-m
(5.3 lb.-in.)
0.6 N-m
(5.3 lb.-in.)
M10
(1)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2)
Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.
(3)
Not all terminals present on all drives.
(4)
Refer to the terminal block label inside the drive.
(5)
Auxiliary power:
UL Installation - 300V DC,
±10%, Non UL Installation - 270-600V DC, ±10%.
Frame 1-6, 100 W