Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 100
3-46
Programming and Parameters
345
Drive OL JnctTmp
Displays the calculated junction temperature of the power semiconductors in the inverter.
The calculation uses the values of Par 313 [Heatsink Temp], Par 358 [Iq Ref Limited], and
inverter thermal characteristics contained in the power EE memory. If this value exceeds
the maximum junction temperature (visible in Par 348 [Drive OL TP Data] when Par 347
[Drive OL TP Sel] = 12 “fJunTmprMax”), two faults occur: Inverter Overtemperature Fault
(fault code 15), and Junction Overtemperature Fault - indicated by bit 7 [Jnc OverTemp] of
Par 346 [Drive OL Status].
Units:
Default:
Min/Max:
degC
0.0000
-50.0000/300.0000
Real
346
Drive OL Status
Indicates the status of various overload (OL) conditions.
• Bit 0 [NTC Shorted] indicates the Negative Temperature Coefficient (NTC) device has a short circuit.
• Bit 1 [NTC Open] indicates the NTC has an open circuit.
• Bit 2 [HS OverTemp] indicates that the heatsink temperature is above 105C for ratings 1.1-11.0A, 115C for 14-34A, or 100C for 40-52A.
• Bit 3 [HS Pending] indicates that the heatsink temperature is above 95C for ratings 1.1 -11A, 105C for 14- 34A, or 90C for 40- 52A.
• Bit 4 [IT Trip] indicates the drive has exceed the 3 second rating of either the 150% normal duty rating or 200% of the heavy duty rating.
• Bit 5 [IT Pending] indicates the drive OL integrator is at 50% of the time out time.
• Bit 6 [IT Foldback] indicates the drive closed loop current limit is in a fold back condition. The value of the fold back is proportional to the calculated junction
temperature.
• Bit 7 [Jnc Over Temp] indicates the junction temperature has exceeded the maximum temperature for the power semiconductor device.
347
Drive OL TP Sel
Enter or write a value to select the drive overload data displayed in Par 348 [Drive OL TP
Data].
Default:
Options:
0
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
“Zero”
“Zero”
23 “fIgbtJuncase”
“fAbsIsCurr”
24 “fIgbtWatts”
“fDelta”
25 “iIgbtPerMod”
“fAbsIqCurr”
26 “fFdThres”
“fOL_l”
27 “fFdSlope”
“fOL_m”
28 “fFdJunCase”
“fOL_k”
29 “fFdWatts”
“fOL_g”
20 “fMaxHsDegc”
“fOL_intg”
31 “fCsImp”
“fCL_intg”
32 “fCsFltr”
“fInvOLClim”
33 “fPwmHz”
“fJuncDegc”
34 “fElecHz”
“fJunTmprMax”
35 “fModIdex”
“f60sPUCur”
36 “fBoost”
“f60sAmp”
37 “fTotalWatts”
“f3sPUCur”
38 “fHSDegc”
“f3sAmp”
39 “iAdconv”
“fRatioInvMtr”
30 “Jct Temp 700S”
“fRatioMtrInv”
41 “Jct Tmp HiHp”
“iConvertStat”
42 “Jct Tmp FWD“
“fIgbtThres”
43 ”HH Lss Intg”
“fIgbtSlope”
44 “HH PwrBdTemp”
“fIgbtEnergy”
348
Drive OL TP Data
Displays the value selected by Par 347 [Drive OL TP Sel].
Default:
Min/Max:
0.0000
-/+2200000000.0000
Real
350
Iq Actual Ref
Displays the value of motor current reference that is present at the output of the divide by
flux calculation.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
Real
351
Iq Ref Trim
Provides an external source to command, trim or offset the internal motor current
reference. This value is summed with Par 350 [Iq Actual Ref] before the current limit is
applied. Scaling is in per unit motor current.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
✓ ✓ Real
352
Is Actual Lim
Displays the largest allowable stator motor current. The range of allowable motor current
is limited by the maximum drive current. Scaling is in per unit motor current.
Units:
Default:
Min/Max:
P.U.
1.0000
0.0000/8.0000
Real
353
Iq Actual Lim
Displays the largest allowable torque producing (Iq) motor current. The range of allowable
Iq motor current is limited by the maximum drive current and is adjusted by the motor flux
current. Scaling is in per unit Iq motor current.
Units:
Default:
Min/Max:
P.U.
1.0000
0.0000/8.0000
Real
354
Iq Rate Limit
Enter the maximum rate of change for Current Reference, in per unit current/ sec. Par 90
[Spd Reg BW] will be limited to 2/3 of this value.
Units:
Default:
Min/Max:
/Sec
1000.0000
5.0000/10000.0000
✓ ✓ Real
355
Iq Rate Limited
Displays the current reference output of the rate limiter.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
Real
No.
Name
Description
Values
Li
nkab
le
Read
-Wr
it
e
Da
ta
T
ype
Options
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Jnc
Ov
er
Te
m
p
IT
F
oldbac
k
IT
P
ending
IT
T
ri
p
HS P
end
in
g
HS Ov
erT
emp
NTC Open
NTC Shor
ted
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True