Appendix c - application notes, Input voltage range/ tolerance, Appendix c – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 211: Application notes, Appendix
Appendix
C
Application Notes
For additional application notes, refer to the PowerFlex 700S Adjustable
Frequency AC Drive with Phase I Control - Reference Manual, publication
PFLEX-RM002.
Input Voltage Range/
Tolerance
For Information on …
See Page...
Drive Rating
Nominal Line
Voltage
Nominal Motor
Voltage
Drive Full Power
Range
Drive Operating
Range
200-240
200
200†
200-264
180-264
208
208
208-264
240
230
230-264
380-400
380
380†
380-528
342-528
400
400
400-528
480
460
460-528
500-600
(Frames 1-4 Only)
600
575†
575-660
432-660
500-690
(Frames 5 & 6 Only)
600
575†
575-660
475-759
690
690
690-759
475-759
Drive Full Power Range =
Nominal Motor Voltage to Drive Rated Voltage + 10%.
Rated current is available across the entire Drive Full Power
Range
Drive Operating Range =
Lowest† Nominal Motor Voltage - 10% to Drive Rated Voltage +
10%.
Drive Output is linearly derated when Actual Line Voltage is less
than the Nominal Motor Voltage
HP
@ Motor (Drive Output)
Actual Line Voltage (Drive Input)
Full Power Range
Drive Operating Range
Nominal Motor Voltage -10%
Nominal Motor Voltage
Derated Power Range
No Drive
Output
Drive Rated Voltage
Drive Rated Voltage +10%