Led indications, Led indications -2 – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 156
4-2
Troubleshooting
LED Indications
Figure 4.1 Drive Status Indicators
Table 4.A Drive Status Indicators
DRIVE
DRIVE
SYNCHLINK
ENABLE
3
2
1
4
Frame 1 Shown
#
Name
Color
State
Description
Action
DR
IV
E
Po
w
er
S
tr
uc
tu
re
➊
PWR
(Power)
Green
Steady
Illuminates when power is applied to the drive.
No action - no faults present
➋
STS (Status)
Green
Flashing
Drive ready, but not running & no faults are
present.
No action - no faults present
Steady
Drive running, no faults are present.
No action - no faults present
Yellow
Flashing
A type 2 (non-configurable) alarm condition
exists, drive continues to run.
A run inhibit exists. Refer to
Steady
A type 1 (user configurable) alarm condition
exists, but drive continues to run.
Red
Flashing
A fault has occurred.
Refer to Table for faults.
Steady
A non-resettable fault has occurred.
Red /
Yellow
Flashing
Alternately
The drive is in flash recovery mode. The only
operation permitted is flash upgrade.
Complete Flash Upgrade
Con
trol As
se
mb
ly
Communi
cati
ons
➌
PORT
Refer to the
Communication
Adapter User
Manual
Status of DPI port internal communications (if
present).
MOD
Status of communications module (when
installed).
NET A
Status of network (if connected).
NET B
Status of secondary network (if connected).
Contro
l
➍
SYNCHLINK Green
Steady
• The module is configured as the time keeper
or
• The module is configured as a follower and
synchronization is complete.
Green
Flashing
The follower(s) are not configured with the time
keeper.
Red
Flashing
• The module is configured as a time master
on SynchLink and has received time
information from another time master on
SynchLink.
ENABLE
Green
On
The drive’s enable input is high.