Chapter 2 - start-up, Prepare for drive start-up, Before applying power to the drive – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 51: Chapter 2, Start-up, Prepare for drive start-up -1, Before applying power to the drive -1, Chapter

Chapter
2
Start-Up
This chapter describes how you start-up the PowerFlex 700S Drive. Refer to
for a brief description of the HIM (Human Interface Module).
Prepare for Drive Start-Up
Before Applying Power to the Drive
Important: If you have a DriveLogix application, you must first connect
the battery before starting this section.
❏ 1. Confirm that motor wires are connected to the correct terminals and are
secure. Confirm Frame 5 transformer connections (refer to
❏ 2. Confirm that encoder wires are connected to the correct terminals and
are secure.
❏ 3. Confirm that all control inputs are connected to the correct terminals and
are secure.
❏ 4. Verify that AC line power at the disconnect device is within the rated
value of the drive.
❏ 5. Verify that control power voltage is correct.
The remainder of this procedure requires that a HIM be installed. If an
operator interface is not available, remote devices should be used to start-up
the drive.
For Information on …
See Page...
!
ATTENTION: Power must be applied to the drive to perform
the following start-up procedure. Some of the voltages present are
at incoming line potential. To avoid electric shock hazard or
damage to equipment, only qualified service personnel should
perform the following procedure. Thoroughly read and
understand the procedure before beginning. If an event does not
occur while performing this procedure, Do Not Proceed.
Remove Power including user supplied control voltages. User
supplied voltages may exist even when main AC power is not
applied to then drive. Correct the malfunction before continuing.